Product Details:
Brand | Motwane |
Model | PCRM-100S |
Application | Circuit Breaker contact resistance Electrode resistance measurement Bus bar joints Isolator contacts Weld joints Bond resistance |
Operating Temperature in Degree Celsius | 0 to 55 |
Mains | 230V +/- 10%, 50Hz +/- 10Hz Single phase AC supply |
Battery | 12V-7.5AH Rechargeable) |
Power Consumption | 35VA, 6.0 Watt on battery |
Measurement Principle | Four wire measurement |
PC Interface | Through USB |
Printer | Built in Thermal Printer for Test Results |
Test Currents | 100A DC |
Internal Memory | 99 Test Results |
Display | Custom Built 3 1/2 Digit LCD Display with Backlit |
Basic Accuracy | 2 Percent of reading +/- 1 Digit |
Enclosure Material | ABS |
Applications
PCRM-100S is specially used to measure static contact resistance of HT circuit breaker contacts installed in live
energised swithcyards. HIgh accuracy and repeatability makes it a reliable tool for Quality Assurance and easy operation makes it a very handy tool for quick maintenance checks in various industries.
Typical resistance measurement applications are
Physical Specifications
Safety Standard
Additional Information:
Product Details:
Brand | Motwane |
Model | PCRM200S |
Application | Laboratory, BUS Bar Joint,Isolator Contacts,Weld Joints,Bond Resistance, Industrial |
Display | Custom Built 3 1/2 Digit LCD Display with Backlit |
Test Current Injection | 100A & 200A DC |
Measurement Principle | Four Wire Measurement |
PC Interface | Through USB |
Test On Alert | Beep |
Memory Storage | 199 Reading storage facility |
Thermal Printer | For Printing the Test Results |
Basic Accuracy | +-2 Percent of Reading |
Power Supply | Mains & Battery-12V-7.2AH (Rechargeable) |
Applications:
PCRM-200S is specially used to measure static contact resistanceof circuit breaker contacts installed in live energized switch yards.
Typical resistance measurement applications are:
Physical Specifications
Additional Information:
Product Details:
Model | CRM100A |
Brand | MOTWANE |
Principle | 4 Wire Measurement |
Test ON Indication | LED and Beep |
Current Injection | Steps of 10A, 20A, 50A & 100A |
Open-Circuit Voltage | 5V DC |
Resistance Measurements | 200 micro ohms to 20 mega ohms |
Display | 3 1/2 Digit Large LCD Display |
Keypad | Heavy Duty Sealed Soft Touch Membrane Keypad |
Over Range Indication | Blinking OL Display |
Resolution | 0.1 |
Output power | 500VA |
Physical Specifications
Additional Information: